NCS-TT108 smart temperature transmitter, using the fieldbus technology, is a new generation of smart fieldbus temperature transmitter and it is an indispensable field device for process control. NCS-TT108 transmitter integrates abundant function blocks and realizes not only general measurement function but also complicated control strategy.
NCS-TT108 smart temperature transmitter supports eight-channel temperature sensor input. It applied to a variety of thermal resistance and thermocouple sensors and has wide range. NCS-TT108 supports FF, and PA protocols. It can be widely used in the petroleum, chemicals, electricity, and metallurgical industries, etc.
● | Support many types of thermal resistance and thermocouple sensors | ||
● | Thermal resistance supports 2/3 wiring connection mode | ||
● | Thermocouple can use cold end compensation function | ||
● | Support FF, PA protocols |
Input Signal | Resistance: PT100, CU50, CU100, 0~500Ω, 0~4000Ω Thermocouple: B, E, J, N, K, R, S, T Voltage signal: -100mV~100mV | ||
Channel | 8-channel | ||
RTD Wiring | 2-wire, 3-wire | ||
Bus Power | 9~32 VDC Current consumption (static): ≤20mA | ||
Isolation | Between input channel and bus: 500Vrms (707 VDC) Between temperature converter module: 500Vrms (707 VDC) The two temperature input channels in the module are not isolated. | ||
Working Temperature | -40℃~85℃ | ||
Humidity Range | 0%~100%RH | ||
Start Time | ≤5s | ||
Refresh Time | 0.2s | ||
Protection | IP20; Outside box IP67 | ||
Vibration | Arbitrary axial 0~200Hz, error is±0.05%/g of largest range | ||
EMC | Bus terminal: GB/T 18268-2000 Table A1 Sensor terminal: GB/T 18268-2000 Table 1 |
NCS-TT105 smart temperature transmitter,
using the fieldbus technology, is a new generation of smart fieldbus temperature transmitter and it is an indispensable field device for process control.
NCS-TT105 transmitter integrates abundant function blocks and realizes not only general measurement function but also complicated control strategy.
NCS-TT105 uses digital technology, so it can connect with many types of thermocouple and thermo resistive sensors. It has wide range and simple interface between field and control room, which reduces the expense of installation, operation and maintenance.
NCS-TT105 supports HART, FF, and PA protocols. It can be widely used in the petroleum, chemicals, electricity, and metallurgical industries, etc.
Size of NCS-TT105 Temperature transmitter
Figure: Size of NCS-TT105 temperature transmitter (unit: mm)
NCS-TT106 temperature transmitter supports FF H1, PROFIBUS PA and HART protocols and multiple temperature sensors. With independent R&D communication controller, it has become a fieldbus temperature transmitter with high performance.
● | Support multiple thermal resistance and thermocouples | ||
● | Thermal resistance supports 2/3/4-wire connection mode | ||
● | Thermocouple can use cold end compensation function | ||
● | Better accuracy: PT100 ±0.3 ℃; K-type ±0.4 ℃ | ||
● | Universally programmable for various input signals | ||
● | Available protocols: HART /FF H1 /PROFIBUS PA |
NCS-TT106H HART
Pt100、Pt1000、CU50、CU100、0~500Ω、0~4000Ω B,E,J,N,K,R,S,T eight kinds of Thermocouple -100mV~100mV voltage signal0 | |
Channel | Single |
RTD Wiring | 2-wire, 3-wire, 4-wire |
Bus Power | HART: 11~35 VDC |
Bus Signal | HART,current mode |
Electric isolation | 1000VAC |
Working Temperature | -40℃~85℃ |
Humidity Range | 5%~95%RH |
Start Time | ≤5s |
Refresh Time | 0.5s |
EMC | GB/T 18268.1-2010 |
Protection | Terminal IP00, housing IP40 |
Voltage effect | ±0.005%/V |
Alarm signal | Alarm output can be set as 3.5…23 mA Upper/lower limit current 20.8mA / 3.8mA |
Current accuracy | 0.03% |
RTD Parameter
RTD Parameter at Normal Temperature
Signal type | Suggested range | Accuracy(25℃) | Temperature drift(per ℃) |
Resistance Signal | 0~500Ω | ±0.04Ω | ±0.001Ω |
0~4000Ω | ±0.35Ω | ±0.015Ω | |
PT100 | -200 ~ 850℃ | ±0.15℃ | ±0.003℃ |
PT1000 | -200 ~ 850℃ | ±0.15℃ | ±0.005℃ |
CU50 | -50 ~ 150℃ | ±0.15℃ | ±0.005℃ |
CU100 | -50~ 150℃ | ±0.10℃ | ±0.003℃ |
Thermocouple
Thermocouple Parameter at Normal Temperature
Signal type | Suggested range | Accuracy(25℃) | Temperature drift(per ℃) |
mV | -100mV ~ +100mV | ±0.025mV | ±0.001 mV |
B | 500 ℃~ 1810℃ | ±0.77℃ | ±0.050℃ |
E | -200 ℃~ 1000℃ | ±0.20℃ | ±0.025℃ |
J | -190 ℃~ 1200℃ | ±0.35℃ | ±0.01℃ |
K | -200℃ ~ 1372℃ | ±0.40℃ | ±0.025℃ |
N | -190℃ ~ 1300℃ | ±0.50℃ | ±0.015℃ |
R | 0℃ ~ 1768℃ | ±0.75℃ | ±0.023℃ |
S | 0 ℃~ 1768℃ | ±0.70℃ | ±0.023℃ |
T | -200℃ ~ 400℃ | ±0.35℃ | ±0.015℃ |
NCS-TT106F Foundation Fieldbus
Bus interface | FF |
Bus power | 9~32VDC |
Input Signal | Pt100、Pt1000、CU50、CU100、0~500Ω、0~4000Ω Resistance; B E J K N R S T Thermocouple、-100mV~100mV、Custom defined TC、Custom defined RTD |
Channel | Single |
RTD Wiring | 2-wire, 3-wire, 4-wire |
Refresh Time | 0.5s |
Working Temperature | -40~85℃ |
Storage temperature | -40~85℃ |
Humidity Range | 5~95%RH |
Electric isolation | 1000VAC |
Voltage effect | ±0.005%/V |
Protection | Terminal IP00, housing IP40 |
EMC | GB/T 18268.1-2010 GB/T 18268.25-2010 |
RTD Parameter
RTD Parameter at Normal Temperature(25℃)
Signal type | Suggested range | Accuracy(25℃) | Temperature drift(per ℃) |
Resistance Signal | 0~500Ω | ±0.04Ω | ±0.001Ω |
0~ 4000Ω | ±0.35Ω | ±0.015Ω | |
PT100 | -200~850℃ | ±0.15℃ | ±0.003℃ |
PT1000 | -200~850℃ | ±0.15℃ | ±0.005℃ |
CU50 | -50~150℃ | ±0.15℃ | ±0.005℃ |
CU100 | -50~150℃ | ±0.10℃ | ±0.003℃ |
Thermocouple
Thermocouple Parameter at Normal Temperature(25℃)
Signal type | Suggested range | Accuracy(25℃) | Temperature drift(per ℃) |
mV | -100mV~+100mV | ±0.025mV | ±0.001 mV |
B | 500℃~1810℃ | ±0.77℃ | ±0.050℃ |
E | -200℃~1000℃ | ±0.20℃ | ±0.025℃ |
J | -190℃~1200℃ | ±0.35℃ | ±0.01℃ |
K | -200℃~1372℃ | ±0.40℃ | ±0.025℃ |
N | -190℃~1300℃ | ±0.50℃ | ±0.015℃ |
R | 0℃~1768℃ | ±0.75℃ | ±0.023℃ |
S | 0℃~1768℃ | ±0.70℃ | ±0.023℃ |
T | -200℃~400℃ | ±0.35℃ | ±0.015℃ |
NCS-TT108 smart temperature transmitter, using the fieldbus technology, is a new generation of smart fieldbus temperature transmitter and it is an indispensable field device for process control. NCS-TT108 transmitter integrates abundant function blocks and realizes not only general measurement function but also complicated control strategy.
NCS-TT108 smart temperature transmitter supports eight-channel temperature sensor input. It applied to a variety of thermal resistance and thermocouple sensors and has wide range. NCS-TT108 supports FF, and PA protocols. It can be widely used in the petroleum, chemicals, electricity, and metallurgical industries, etc.
● | Support many types of thermal resistance and thermocouple sensors | ||
● | Thermal resistance supports 2/3 wiring connection mode | ||
● | Thermocouple can use cold end compensation function | ||
● | Support FF, PA protocols |
Input Signal | Resistance: PT100, CU50, CU100, 0~500Ω, 0~4000Ω Thermocouple: B, E, J, N, K, R, S, T Voltage signal: -100mV~100mV | ||
Channel | 8-channel | ||
RTD Wiring | 2-wire, 3-wire | ||
Bus Power | 9~32 VDC Current consumption (static): ≤20mA | ||
Isolation | Between input channel and bus: 500Vrms (707 VDC) Between temperature converter module: 500Vrms (707 VDC) The two temperature input channels in the module are not isolated. | ||
Working Temperature | -40℃~85℃ | ||
Humidity Range | 0%~100%RH | ||
Start Time | ≤5s | ||
Refresh Time | 0.2s | ||
Protection | IP20; Outside box IP67 | ||
Vibration | Arbitrary axial 0~200Hz, error is±0.05%/g of largest range | ||
EMC | Bus terminal: GB/T 18268-2000 Table A1 Sensor terminal: GB/T 18268-2000 Table 1 |
TT106H-R Din rail temperature transmitter with dual channel input. Channel 1 can connect up to 4 lines of RTD, channel 2 can connect up to 3 lines of RTD, and channel 1 and channel 2 can be connected to TC signal at the same time.
NCS-TT106H-R1 HART single channel Din Rail temperature transmitter, using the fieldbus technology, is a
new generation of smart fieldbus temperature transmitter and it is an indispensable field device for process control.
NCS-TT106H-R1 HART single channel Din Rail temperature transmitter integrates abundant function
blocks and realizes not only general measurement function but also complicated control strategy.
NCS-TT106H-R1 HART single channel Din Rail temperature transmitter uses digital technology, so it can
connect with many types of thermocouple and thermo resistive sensors. It has wide range and simple
interface between field and control room, which reduces the expense of installation, operation and maintenance.
NCS-TT106H-R1 HART single channel Din Rail temperature transmitter supports HART, FF, and PA protocols.
It can be widely used in the petroleum, chemicals, electricity, and metallurgical industries, etc.