Fieldbus Converter

NCS-IF105 Current/Fieldbus Converter

NCS-IF105 Current/Fieldbus Converter

NCS-FI105 Fieldbus/Current Converter

 

Product Description

As a conversion device, NCS-IF105 converter can receive 4~20mA analog signal of 4 channels and convert to Foundation fieldbus or profibus PA signal.

 

Size of NCS-IF105 Converter

Figure 1  Size of NCS-IF105 Converter (unit: mm)

Specifications
Input signal
4~20mA
Channels
4 Channels
Power supply
9 ~ 32 VDC 
Current Dissipation (static)
≤ 14mA
Fieldbus Signal
Communication Baudrate 31.25kbit/s, current-mode
Insulation
Between housing and terminal board:500 Vrms (707 VDC)
Display
6 bits digital number and 5 bits characters LCD display (Optional)
Temperature range
- 40 ~ 85°C(No display); - 30 ~ 70°C(display)
Humidity Range
0% ~ 100% RH
Start Time
≤ 5s
Protection Grade
IP 65
EMC
Designed to comply IEC 61000
Accuracy
< 0.05 %;
Input Impedance
150 Ω
Temperature Effect 
< ± 50 ppm/℃
Electrical connection 
1/2 - 14 NPT

 

 

 

Product Description

As a conversion device, NCS-IF105 converter can receive 4~20mA analog signal of 4 channels and convert to Foundation fieldbus or profibus PA signal.

 

Size of NCS-IF105 Converter

Figure 1  Size of NCS-IF105 Converter (unit: mm)

Specifications
Input signal
4~20mA
Channels
4 Channels
Power supply
9 ~ 32 VDC 
Current Dissipation (static)
≤ 14mA
Fieldbus Signal
Communication Baudrate 31.25kbit/s, current-mode
Insulation
Between housing and terminal board:500 Vrms (707 VDC)
Display
6 bits digital number and 5 bits characters LCD display (Optional)
Temperature range
- 40 ~ 85°C(No display); - 30 ~ 70°C(display)
Humidity Range
0% ~ 100% RH
Start Time
≤ 5s
Protection Grade
IP 65
EMC
Designed to comply IEC 61000
Accuracy
< 0.05 %;
Input Impedance
150 Ω
Temperature Effect 
< ± 50 ppm/℃
Electrical connection 
1/2 - 14 NPT

 

 

Product Description

NCS-FI105 fieldbus to current Converter is used to convert fieldbus signals to conventional analog signals. It can receive fieldbus signals, and convert them to 4-channel 4~20mA analog signals. NCS-FI105 is the converter between fieldbus system and control valve/other actuator. 

As a conversion device, NCS-FI105 converter can receive Foundation fieldbus or profibus PA signal and convert to 4~20mA analog signal of 4 channels.

1.1kg
How it Works

Dimension (Unit:mm)

Wiring

The power and signal of NCS-FI105 converter Transmitter are sharing one pair of cables (Bus Cable). 

 

Specifications
Output of signal
4~20mA
Channels
4 Channels
Power supply
9 ~ 32 VDC 
Current Dissipation (static)
≤ 14mA
Fieldbus Signal
Communication Baudrate 31.25kbit/s, current-mode
Insulation
Between housing and terminal board:500 Vrms (707 VDC)
Display
6 bits digital number and 5 bits characters LCD display (Optional)
Temperature range
- 40 ~ 85°C(No display); - 30 ~ 70°C(display)
Humidity Range
0% ~ 100% RH
Start Time
≤ 5s
Protection Grade
IP 65
EMC
Designed to comply IEC 61000
Accuracy
< 0.05 %;
Maximum load
1350Ω
Load power
9 ~ 32VDC, Note:supply voltage ≥ (output current * load resistance + 5VDC) 

Temperature Effect 
< ± 50 ppm/℃
Electrical connection 
1/2 - 14 NPT
Material of Construction 
Aluminum
Weight
1.1kg

 

 

Installation 
For installation of NCS-FI105 converter, three types of bracket (pipe mounting flat bracket, plate mounting angle bracket and pipe mounting angle bracket) are provided. Accordingly there are three installation methods as the following. 

The installation of pipe mounting flat bracket: the typical installation as Figure 2.1 shows. Fix NCS-FI105 converter in flat bracket using four bolts provided, and then fix the flat bracket on the vertical pipe in Φ50mm around through the U-shape bolt provided.

The installation of plate mounting angle bracket: the typical installation as Figure 2.2 shows. Fix NCS-FI105 converter in angle bracket using four bolts provided, and then fix the angle bracket on the plate through the M10 bolt not provided.

The installation of pipe mounting angle bracket: the typical installation as Figure 2.3, 2.4 shows. Fix NCS-FI105 converter in angle bracket using four bolts provided, and then fix the angle bracket on the horizontal pipe in Φ50mm around through the U-shape bolt provided.

Wiring
The power and signal of NCS-FI105 converter Transmitter are sharing one pair of cables (Bus Cable). NCS- FI105 converter is suggested to use specific Fieldbus cables recommended by the IEC61158-2. The wiring terminal is at the rear cover side, the wiring terminal board could be seen when the rear cover is screwed.

Figure 2.5 The wiring terminal board of NCS-FI105 Converter 

Figure 2.6 Wiring of NCS-FI105 Converter  
Signal wires should be passed the wire hole. Sensor signal wires are single-point grounding. The Shield of the bus cable should be floating in converter side, and be grounding in bus power side. 

The signal and bus cable should not share the line pipe or trunkings with other equipment, and should stay away from high-power equipment

TEL:
0086-24-31217278
0086-24-31217280
Fax:
0086 24 31217293
E-MAIL:
jin.guangshu@microcyber.cn
Address:
17-8 Wensu Street, Hunnan New District, Shenyang, China.
Zip:110179